Tech performed CMA FULL SERVICE on 6 split systems and 2 mini splits. Tech found Cond 3 TA2F fan pulling 1.7 rated for 1.3. AHU 2 down due to a failed thermostat. Thermostat is blank but is receiving 24v. RTU is down and has not ran since last CMA visit. Office is sending over repair quote. Tech sent email with other estimates attached.
Swansboro, NC 28584
Joseph C.
Joseph C. Checked in
Tech found fire panel throwing trouble code not allowing system to come on. Tech found smoke detector was modified with hose on the end tech took off and discovered it was cut, detector will need to be replaced. Compressor 1 is still shorted to ground compressor 1 contractor melted and missing 80amp fuse. All was diagnosed last August, tech informed management to call alarm company regarding alarm issue and we need to quote for repairs. Tech recommends replacing system due to all challenges and age.
Swansboro, NC 28584
David  S.
David S. Checked in
-Performed CMA Full Service on 9 Rooftop Package Heat Pumps, 5 Mini Split Heat Pumps, and inspection of 2 hanging heaters. -RTU-1: Did not observe condenser fan motor #2 operate with call from thermostat or with unit in test mode. Verified connectivity at previous splice for motor. Confirmed problem is with motor by swapping connections with other motor. Recommend replacement of condenser fan motor 1/2 hp 480v. Provided estimate for replacement of motor. -RTU-6: Pulley and belt off of exhaust air blower. Recommend demand tech to diagnose/identify needed repairs upon request. -RTU-7: Bottom outdoor fan motor capacitor tested below threshold. Recommend replacement of capacitor. Provided estimate for replacement of 25 mfd capacitor. Replaced with on site approval from Daniel. Circuit 2 compressor jars when coming on. System diagnosed with leak in evaporator coil Feb 2024. -RTU-8: Circuit 1 compressor does not operate. System circuit 1 diagnosed as void of refrigerant Feb 2024. -RTU-9
Swansboro, NC 28584
Kyle W.
Kyle W. Checked in
Tenant stated system has not been keeping temperature inside home. Found system low on charge. Oily substance within auxiliary drain pan. Located (2) areas within evaporator coil leaking. System has also had intermittent challenges with variable speed condenser fan motor as well. Unable to duplicate at this time, but motor may be failing based on past findings with another company. Spoke with Kevin. Built estimate for repairs. Costly repairs may not be recommended. System is out of warranty. Requested field supervisor to quote system replacement as well. Will call when a decision is made with homeowner.
Swansboro, NC 28584
David  S.
David S. Checked in
-Dispatched to identify problems with Mini Split heat Pump in Data/Server Room. Dispatch states massive refrigerant leak. System was cooling with only a 12 degree temperature difference at last service. Maintenance not on site at time of arrival. -Found air handler in server room not operating. Unable to identify any leaks with sniffer at evaporator coil. Found no high voltage at air handler. Found no high voltage at condenser in middle courtyard. Found no continuity through time delay fuses in disconnect. -Found compressor failed megohm test on all 3 terminals. Found compressor shorted to ground. Compressor has failed and unit is non operational. Customer should consider cost of compressor replacement versus price of system replacement. Other issues may be present in system pending compressor replacement. Field supervisor should provide options for customer.
Swansboro, NC 28584
David  S.
David S. Checked in
-Performed CMA Filter Change on 6 Split System Air Handlers & 1 Rooftop Package Unit. Cleaned filters on 2 mini splits. -Management states no one on site to provide access for rooftop unit. Requested that filters be left for maintenance to replace another day.
Swansboro, NC 28584
Derek J.
Derek J. Checked in
Leveled air handler.
Swansboro, NC 28584
Derek J.
Derek J. Checked in
Tech got information off CFD-15 butterfly dampers for office to order new fuse links. Need 10 in total to make repairs
Swansboro, NC 28584
David  S.
David S. Checked in
-Performed CMA Full Service on 19 split systems and 2 mini split systems. Verified operation of oven hood exhaust fan and make up air. -Split System 1: Outdoor fan motor capacitor tested weak at prior visit. Recommend replacement of capacitor. -Split System 2: Outdoor unit turned off at disconnect. System previously diagnosed for shorted indoor fan causing transformer to burn up (7/31/23). Did not operate system at time of service. System not operational. -Split System 3: Outdoor fan motor capacitor tested weak at prior service. Recommend replacement of capacitor. -Split System 4: Found heat strip contactor coils show signs of severe heat damage at last service. Corrosion on backs on heat strips contactors. Recommend replacement of contactors. -Split System 6: Outdoor disconnect left off at prior service due to diagnosis for system void of refrigerant (7/31/23). Did not opera
Swansboro, NC 28584
David  S.
David S. Checked in
-Returned to replace time delay relay & control board per prior approval as recommended Sep 2023. -Diagnosis on Sep 22, 2023: Found no call at new contactor on compressor circuit. Verified voltage from transformer and call from thermostat. Time delay relay board not operating as intended, therefore not providing 24v call on Y circuit to contactor. Temporarily bypassed time delay relay board to provide operation of system. Recommend replacement of time delay relay & board. -System is still not operational per diagnosis Nov 27, 2023: Found circuit breaker for air handler tripped upon arrival. Found thermostat had wrong setting for reversing valve. Was cooling in heat mode and heating in cool mode. Corrected setting and verified modes of operation. Supply damper fuse links caused dampers to close at 10 locations. Recommend replacement of damper fuse links. Causing a complete lack of air flow in system. System to be left off until repair can be made. -Replaced relay board per prior app
Swansboro, NC 28584
David  S.
David S. Checked in
-Returned to replace time delay relay & control board per prior approval as recommended Sep 2023. Tech was provided with defrost control board, not time delay board. -Diagnosis on Sep 22, 2023: Found no call at new contactor on compressor circuit. Verified voltage from transformer and call from thermostat. Time delay relay board not operating as intended, therefore not providing 24v call on Y circuit to contactor. Temporarily bypassed time delay relay board to provide operation of system. Recommend replacement of time delay relay & board. -System is still not operational per diagnosis Nov 27, 2023: Found circuit breaker for air handler tripped upon arrival. Found thermostat had wrong setting for reversing valve. Was cooling in heat mode and heating in cool mode. Corrected setting and verified modes of operation. Supply damper fuse links caused dampers to close at 10 locations. Recommend replacement of damper fuse links. Causing a complete lack of air flow in system. System to be left
Swansboro, NC 28584
David  S.
David S. Checked in
Replace indoor fan motor on AH-4 as previously diagnosed and approved. Verified operation of fan and system heating via heat pump.
Swansboro, NC 28584
Kyle W.
Kyle W. Checked in
PERFORMED CMA INSPECTION ON (6) TRANE SPLIT HEAT PUMPS, (2) MINI SPLIT SYSTEMS, AND (1) DUAL FUEL RTU SYSTEM. FOUND CONDENSER #5 FAN BLADE IS CRACKED. BUILT ESTIMATE ON REPLACEMENT. SYSTEMS #2, #3, #5 RECOMMEND AC RENEW DUE TO NOISEY COMPRESSORS. ADDED TO ESTIMATE. SPOKE WITH CATHERINE SHE WILL GET APPROVAL.
Swansboro, NC 28584
Noah C.
Noah C. Checked in
Upon arrival tech was informed of bacterial buildup on supply vents in part department as well as employees in this are that are getting sick during the work week. Tech inspected system and found challenges at RTU4. Tech removed supply vents from supply line in parts room and found inside of duct to be clean and registers to be insulated. Tech found system to be running in cool mode set at 68. If system is running in cool mode most of the year this will cause supply registers to condensate being there is warm air mixing with supply registers. Also thermostat is located in electrical room conditioned by a mini split. Tech recommended cleaning all supply registers and installing a Plasma Pure Air Purifier to improve air quality in this area. Quoted $881.45 plus tax for installation of Plasma Pure Air. Quoted $180.62 to clean supply registers (each). Mr. Danny cleaned the supply registers. Tech relocated thermostat per customer request from electrical room to parts department. Tech tested
Swansboro, NC 28584
Luis R.
Luis R. Checked in
Tech found rtu 6 s#481D had a leak in evaporator tech added 2 leak freeze to each circuit system has 2 circuits and added 1lb of 410a to circuit 1. Tech let system run while working on others when tech returned tech did not pick up any more leaks with leak detection at this time. Rtu 7 s# 463D tech opened evaporator coil cabinet to perform leak search and picked up a major leak instantly. Upon further inspection tech found both compressor low of refrigerant enough to indicate leak was snot small tech does not believe leak freeze will help with this system. Rtu 8 s# 475D tech found circuit 1 completely void of refrigerant indicating leak is major and leak freeze will definitely not have any effect. Tech spoke with Daniel Informed him of new findings he instructed tech to not add any more leak freeze and he will go back to his leadership team and relay the findings and call back when they decide what they want proceed with.
Swansboro, NC 28584
Joshua C.
Joshua C. Checked in
Completed a filter change on 6 Trane air handlers, package unit on roof, washed filters on 2 mini splits,
Swansboro, NC 28584
Jesse J.
Jesse J. Checked in
Tech preformed CMA INSPECTION on 9 RTUs, 5 Mini Split Systems, and 2 Gas Hanging Heaters. Upon inspection of RTU #1 Tech found that Heat Strips are non functional due to a previous short that caused a wires to burn. Tech unsure cause of issue. Tech did find that a fuse had been pulled from fuse block. Unsure if these was done to prevent any further damage. Recommend replacing heat strips and fuses to further diagnose issue. Being Heat Strips are 460v Office will have to call with further pricing. Tech removed low voltage wire that controls Auxiliary Heat from board to prevent any further damage. Refrigerant issues still exist for RTU #6, #7, and #8. Leak searches were preformed in Sept. 2023 and Office was supposed to send quote. Mini Split System #3 also still has leak that was diagnosed in Sept. 2023. All other Systems are operating at this time. Tech has attached SYSTEM PERFORMANCE REPORTS to invoice along with pictures.
Swansboro, NC 28584
Chris M.
Chris M. Checked in
-Performed CMA inspection on 19 split systems and 2 mini split systems. Verified operation of oven hood exhaust fan and make up air. -Split System 1: Outdoor fan motor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $198.14. -Split System 2: Outdoor unit turned off at disconnect. System previously diagnosed for shorted indoor fan causing transformer to burn up (7/31/23). Did not operate system at time of inspection. System not operational. -Split System 3: Outdoor fan motor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $202.56. -Split System 4: Fault flash code 4 (Hard lockout). Air handler blower motor has been recommended for replacement (5/26/23). System not operational. System left off at AH-4 disconnect pending replacement of blower motor. Found heat strip contactor coils show signs of severe heat damage. Corrosion on backs on heat strips contactors. Recommend replacement of contactors. Provided estimate $547.63. -Sp
Swansboro, NC 28584
Matthew L.
Matthew L. Checked in
Tech found panels off of AHU3 for kitchen with blower running. Indoor coil is thawed. Reinstalled panels. Threads on drain pan for float switch port are cracked. Got pictures of crack. Used PVC union to remove drain line and thread float switch port back in place. Not leaking. Dennis on site declined adding refrigerant, leak freeze, or doing leak search. He will have maintenance charge system up. Tech emailed quotes. Documented findings. No charge for CMA follow up.
Swansboro, NC 28584
Percy M.
Percy M. Checked in
PERFORMED CMA FULL SERVICE ON 8 SPLIT SYSTEMS AND 1 PACKAGE DUAL FUEL SYSTEMS. ALL SYSTEM RUNNING CORRECTLY EXCEPT SPLIT SYSTEM 3. SPLIT SYSTEM 3 HAD A FROZEN EVAPORATOR COIL, TURNED FAN ON SYSTEM SO COIL CAN UNFREEZE. THERE WILL BE FUTHER DIAGNOSES DONE TO SYSTEM 3.
Swansboro, NC 28584
Norman  A.
Norman A. Checked in
Performed CMA inspection on one rooftop package system. System operating correctly at this time.
Swansboro, NC 28584
Review
Romario was Knowledgeable and friendly. He took the time to explain everything. Great company
Latie - Swansboro, NC 28584
Review
This Company consistently provides quick response times. All staff I have interacted with professional and knowledgeable. Excellent service.
Lisa T - Swansboro, NC 28584
Review
Friendly and knowledgeable staff! I didn’t have to wait long for my appointment. Excellent service.
Lisa T - Swansboro, NC 28584
Review
Professional Service.
Buddy - Swansboro, NC 28584

 

Dependable Service Throughout Eastern NC

When you need heating or air conditioning repairs, maintenance or system replacements, you need a company you can count on for dependability and quality service. Contact us at Jackson & Sons at 919-734-9611. Our professional team of technicians look forward to providing energy efficient and cost effective solutions to keep your home or business comfortable at all times.

Contact Us

Why Jackson & Sons

Licensed, Bonded & Insured
Energy Efficient Experts
Same Day Repairs
5 Star Service
Dependable Warranties
Commercial & Residential Services
img-badge-bbb img-badge-epa img-badge-nate
Request Service
servicedetailscustomerreturningschedule
Details Regarding Your Request...
Contact and Service Location...
You and Your Service Location
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
What Is Convenient For You?
What time of day is best for you?
First Available
Morning
Afternoon
Back Next