Recent Jobs and Reviews in Leland, NC

Our Local Reviews by City

Job Locations and Reviews

Noah C.
Noah C. Checked in
Upon arrival tech found compressor not starting on first attempt and pulling high amps. Installed start kit for testing purposes to assure compressor would start on first attempt, compressor did start first attempt and is running. Gave estimate on repairs. Recommend replacing system due to age and previous findings of system over any repairs. Customer approved estimate, made repairs and tested. System is operating properly at this time.
Leland, NC 28451
Noah C.
Noah C. Checked in
Upon arrival tech inspected system 6 for meeting room and found almost failing dual run capacitor as well as corroded herm wire. Ran system and compressor is failing, megged in red range. Condenser fan motor is also failing amping at 1.5 rated for 1.3. Highly recommend replacing system over making any repairs as system is likely to fail very soon after replacing capacitor. Customer approved repair for capacitor replacement. Replaced capacitor. Informed supervisor to provide quote on system.
Leland, NC 28451
Derek J.
Derek J. Checked in
Upon arrival tech was informed indoor unit was running but outdoor unit was not. Tech found system not receiving line voltage due to a tripped 50 amp breaker in the main panel. Further inspected and found compressor shorted between start and run causing breaker to trip. Office will need to quote to replace compressor and 70mfd capacitor. Condenser breaker is left off but air handler is still running to help circulate air.
Leland, NC 28451
David  S.
David S. Checked in
-Performed CMA Full Service on 6 Split System Heat Pumps and 1 Mini Split Heat Pump. -Mini Split System - 2006 LG 0.5 Ton Split Heat Pump: Elevator Room: No air filters in place, as previously reported. -System 1 - 2023 Goodman 4 Ton Split Heat Pump 7428: 3rd Floor: Damage to drain line between floors, as previously reported. Maintenance has been unable to find contractor to repair damaged pipe since renovations. Maintenance is currently draining condensation into tub and emptying tub as needed. Condensation pump was recommended for replacement prior due to non operation due to physical damage, but would not correct current drainage issue. -System 3 - 2022 Bryant/Carrier 5 Ton Split Heat Pump 4165: Kitchen/Dining: System has been previously recommended for addition of an EZ Trap to condensate drain line to allow proper cleaning & servicing of drain line/trap. Difficult access; additional time and materials needed. Provided updated estimate. -System 4 - 2010 York/Nordyne 2 Ton R22 S
Leland, NC 28451
David  S.
David S. Checked in
-Performed CMA Filter Change at locations needed. No filters in elevator room mini split as previously noted. -Noah (maintenance) inquired about repair to drain line between 2nd and 3rd floor. Suspects drain line was damaged during recent renovations. Asked if Jackson and Sons could provide a quote for repair/replacement. Found pipe penetrates concrete between floors, advised a contractor would likely need to be contacted to perform such demo work. Pictures attached to job. Maintenance has replaced condensate pump at 3rd floor air handler but is currently having to catch condensation with a tub and drain manually. Would like to run a new condensation pipe. -Noah also inquired about an error code showing on pool dehumidifier controller. Found that system is a large refrigeration unit. Jackson and Sons does not service this type of equipment.
Leland, NC 28451
Jesse J.
Jesse J. Checked in
Tech preformed CMA FULL SERVICE on 17 Split Systems and 1 Air Makeup Unit. Split Systems #1, #8, #10 and #11 have been replaced with New Systems and are less than 2 weeks old. *Split System #1 is new system. *Split System #2 is operating at this time with no challenges present but system is 19 years old. *Split System #3 is operating at this time but System was down upon arrival due to low volt fuse being blown. Tech replaced fuse and system began to operate. Tech could not find short in low voltage. Tech also found weak condenser fan capacitor, and recommends replacing. Tech has attached estimate to invoice for cost of repair. *Split System #4 is operating at this time with no challenges present but system is 19 years old. *Split System #5 is operating after blower motor was replaced. Tech was then able to service system and found system was not cooling properly. Tech checked pressures and found system is a little low on refrigerant but did not find leak at this time. Tech recommends
Leland, NC 28451
Dalton  B.
Dalton B. Checked in
UNIT #11-2.5 TON TRANE SPLIT HEAT PUMP
Leland, NC 28451
Jesse J.
Jesse J. Checked in
Tech returned to complete approved repairs. Tech replaced blower capacitors on AHU’s #4 and #16. Tech also replaced multi-speed blower motor on AHU #2 due to over amping found during previous CMA VISIT. Tech also replaced blower capacitor. Tech replaced variable speed blower motor on AHU #5. AHU is operating at this time. Tech has attached pictures of repairs to invoice.
Leland, NC 28451
Dalton  B.
Dalton B. Checked in
UNIT #10-1.5 TON TRANE SPLIT HEAT PUMP
Leland, NC 28451
Dalton  B.
Dalton B. Checked in
UNIT #8- 4 TON TRANE SPLIT HEAT PUMP
Leland, NC 28451
Romario  T.
Romario T. Checked in
Found a 50a breaker off, tech reset the breaker for testing purposes. Amp draws on the condenser unit is within specs, compressor is rated for 24RLA amps and is currently pulling 19.7 due to the heat load and high outdoor ambient temperature. Refrigerant levels within specs. After 10-15 minutes of operation, tech noticed the breaker was getting hot and starting to produce an abnormal smell. Tech turned of the breaker off for safety purposes and recommended to have an electrician test and replace the 50A breaker at the main panel. Tech spoke with Anthony about the findings.
Leland, NC 28451
Juan  R.
Juan R. Checked in
UNIT #1 LOBBY- 4 TON TRANE SPLIT HEAT PUMP
Leland, NC 28451
Demarcus  M.
Demarcus M. Checked in
(2) DAMPERS
Leland, NC 28451
Percy M.
Percy M. Checked in
PERFORMED CMA INSPECTION ON 6 SPLIT SYSTEMS AND 1 MINI SPLIT SYSTEM. DUAL RUN CAPACITOR RATED FOR 70/5mf TESTED AT 57.7 mf on THE 70mf side. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBERS SAVINGS OF $53.33. 70mf CAPACITOR REPLACEMENT WOULD BE $322.61 ALL OTHER SYSTEMS PERFORMING PROPERLY.
Leland, NC 28451
Matthew L.
Matthew L. Checked in
Tech replaced filters.
Leland, NC 28451
Matthew L.
Matthew L. Checked in
Outdoor condenser 7 was off at disconnect. Staff reported lineset on outdoor unit 7 freezing up. Not outdoor coil. Restored power and found high pressure switch tripped in heating mode very quickly. Switched to cooling mode and lineset started freezing up. Tech went in search of AHU 7 to confirm blower operation. Attic access in the middle section of back hallway is for AHU 7. Tech confirmed seized up 3/4 hp 1075 rpm blower motor. Tech recommends replacing 19 year old R22 split system over repairing due to cost of blower replacement, age, and EPA phase out of R22. Let Jeff Cupp know of findings. Need to provide repair vs replacement estimates. Let Gina know.
Leland, NC 28451
Luis R.
Luis R. Checked in
Tech was informed unit 14 thermostat was blank tech found thermostat did have power and system was operating. Upon further inspection tech did find power wires to variable speed blower motor was not tight enough and would loosen up when blower would ramp up causing system to loose low voltage power. Tech ensured connection was secured properly and cycled system. System is operating correctly at this time.
Leland, NC 28451
Jesse J.
Jesse J. Checked in
Tech preformed CMA INSPECTION on 17 Split Systems and 1 Air Makeup unit. Systems #1, #8, #10, #11 are still down from previous diagnoses on 8/29/23 and 10/4/23. Recommendations and Quotes have been sent previously. System #3 is down due to multiple challenges with blower motor, blower control relay and etc. Due to age and multiple challenges, tech recommends replacement system. System #5 is down due to failed blower motor module. Tech has attached estimate to invoice for replacement. System #2 is operating at this time but blower motor is operating over listed FLA, due to age and cost of repairs tech does recommend replacing system. Tech has attached estimate for repair to invoice for cost comparison. Systems #4 and #16 are in need of blower capacitors, tech has attached estimates to invoice for repairs. Mr. Shawn did ask tech about the air flow in laundry room. Tech advise that was priced and sent from previous service call on 10/4/23. Mr. Shawn also asked for a quote on mini split sy
Leland, NC 28451

 

Dependable Service Throughout Eastern NC

When you need heating or air conditioning repairs, maintenance or system replacements, you need a company you can count on for dependability and quality service. Contact us at Jackson & Sons at 919-734-9611. Our professional team of technicians look forward to providing energy efficient and cost effective solutions to keep your home or business comfortable at all times.

Contact Us

Why Jackson & Sons

Licensed, Bonded & Insured
Energy Efficient Experts
Same Day Repairs
5 Star Service
Dependable Warranties
Commercial & Residential Services
img-badge-bbb img-badge-epa img-badge-nate
Request Service
servicedetailscustomerreturningschedule
Details Regarding Your Request...
Contact and Service Location...
You and Your Service Location
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
What Is Convenient For You?
What time of day is best for you?
First Available
Morning
Afternoon
Back Next